System configuration & boards addressing

From Hydrover
Revision as of 23:28, 13 June 2017 by Andrea (talk | contribs) (Andrea ha spostato la pagina System configuration & boards numbering a System configuration & boards addressing senza lasciare redirect)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to: navigation, search

The configuration of a system require two steps:

  • tell to the master how many boards of each type are present
  • assing an address to every board


Master configuration

The steps needed to configure the master of the system are:

  • connect your PC with an USB to Serial adapter to the H6105-D serial port
  • open PuTTY and create a serial connection with this parameters: 115200-N-8-1
  • configure the number of H6105-E boards with ce num command e.g. ce num 1
  • configure the number of H6103 boards with io num command e.g. io num 1
  • configure the number of H6104-P boards with ca num command e.g. ca num 1
  • save the configuration with the save command

The number of boards spans from 0 to 20 and are grouped by board type


Boards addressing

The steps needed to assign an address to a board are:

  • connect your PC with an USB Type-B cable to the USB port of the slave board
  • open PuTTY and create a serial connection with this parameters: 115200-N-8-1
  • configure the address number of the board with bnum command e.g. bnum 0

The boards address spans from 0 to 19 and are grouped by board type